Uninterruptible DC supply (DC UPS), series UGV, according to VDE0510
General
DC- UPS series with secondary switched and modular charging rectifier units. Good efficiency with an imperceptible noise development characterize this very reliable series.
All devices of this series are designed to be full load and short-circuit proof on the side of the charging unit and protected against overload on the battery side by a fuse element.
explanation
The maintenance-free, sealed lead battery, working in standby parallel operation with the regulated rectifier, is charged up to a cell voltage of e.g. 2.27V.
The rectifier is designed to supply the connected consumers under full load and to charge the discharged battery within approx. 10 hours. For peak load times the battery can be included as a power reserve. If the connected load is not a constant load, the full rectifier power can be used as a basis for the determination of the unit power rating. However, the autonomy time to be achieved in this case would remain the same as the connected load (see type list).
In the event of a power failure, the connected loads are supplied from the battery for the specified autonomy time without interruption.
performance characteristics
-
- charging power supply with I-V characteristic, acc. to VDE 41773
- full load/ overload/ short circuit resistance
- mains switch/ mains control lamp (not for chassis version), mains fuse
- V/A-meter analog- Kl. 1% for GR output (not for chassis version)
- mains isolation transformer according to VDE 0551
- battery protection, for 19″ rack as automatic fuse in B- characteristic in the rack front panel
- modular structure of the electronics
- Softstart
- div. additional equipment possible, see section “additional equipment”
Standard types/connection capacities/dimensions
Typ, UGV 24/ A-min | Connection power (W) | Battery (Ah) | Housing dimensions, H*B*T, mm | 19" Insertion 84TE | Chassis dimensions (mm) |
---|---|---|---|---|---|
24V | |||||
05/50 | 105 (120) | 7 | 600*380*210 | 3/260 | 250*240*220 |
05/120 | 90 (120) | 12 | 600*380*210 | 3/260 | 250*240*220 |
05/3,5h | 85 (120) | 18 | 600*380*210 | 4/260 | 340*300*220 |
10/18 | 225 (240) | 7 | 600*380*210 | 3/260 | 250*240*220 |
10/40 | 215 (240) | 12 | 600*380*210 | 3/260 | 250*240*220 |
10/60 | 205 (240) | 18 | 600*380*210 | 4/260 | 340*300*220 |
10/2,5h | 180 (240) | 26 | 600*380*210 | 4/460 | 450*300*220 |
15/10 | 345 (360) | 7 | 600*380*210 | 3/260 | 340*300*220 |
15/30 | 325 (360) | 18 | 500*500*210 | 4/360 | 450*300*220 |
15/90 | 300 (360) | 26 | 500*500*210 | 4/460 | 470*437*220 |
20/15 | 450 (480) | 12 | 500*500*210 | 4/360 | 450*300*220 |
20/45 | 420 (480) | 26 | 500*500*210 | 4/460 | 470*437*220 |
30/12 | 700 (720) | 18 | 600*600*350 | 5/390 | 540*400*220 |
30/25 | 660 (720) | 26 | 600*600*350 | 6/460 | 540*400*220 |
40/17 | 900 (960) | 26 | 600*600*350 | 5/490 | 570*537*220 |
48V | |||||
10/18 | 450 (480) | 7 | 500*500*210 | 4/360 | 470*437*150 |
10/40 | 430 (480) | 12 | 500*500*210 | 4/460 | 470*437*170 |
15/10 | 690 (720) | 7 | 600*600*210 | 5/460 | 570*537*170 |
15/30 | 650 (720) | 15 | 600*600*210 | 5/460 | 570*537*180 |
60V | |||||
10/18 | 560 (600) | 7 | 500*500*210 | 4/360 | 470*437*170 |
10/40 | 540 (600) | 12 | 600*600*210 | 4/460 | 570*537*170 |
15/10 | 860 (900) | 7 | 600*600*210 |
Technical data
Cooling | Convection cooling |
Noise emission | ca.40/50 dBA (not or hardly audible) |
Network connection | 1/N/PE 230V 50Hz +/-10% |
Cable Feeding | Top side, rear side for 19" racks, guided on screw terminals |
Accumulators | Pb-maintenance-free/sealed, nom. life expectancy 5 years, 10 years nominal life expectancy on request |
Perm. ambient temperature | 0°C - 40°C, at 80% relative humidity |
Installation altitude | max. 1000m über NN |
Autonomy | see type list, related to final discharge voltage 1.75V/Z at 20°C |
Voltage constancy | Better than 0,2% |
Power Consistency | Better than 0,2% |
Charging time | approx. 10 hours, with simultaneous consumer full load |
Connected load | See list of types, high peak load coverage possible through buffer operation |
Radio interference suppression | B nach EN55011 |
Dimensions | Other dimensions can be realized on request. |